Emergency / Exit Lights and Portable Extinguishers Inspection
Kitchen Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection
12yr Hydrostatic Test Past Due: (1) Ansul 4.5-Gallon System (2009,2010 Manufacture Date) (Cartridge Needs Replaced) During your most recent Fire Protection Inspection, our technicians noted that one or more of your Fire Suppression Tanks are due for a hydrostatic test per: NFPA 17A: 7.5.1 The following parts of wet chemical extinguishing systems shall be subjected to hydrostatic pressure testing at intervals not exceeding 12 years: Wet Chemical Containers Auxiliary Pressure Containers Hose Assemblies Fire Suppression Tanks are required to be pressure tested using water or some other non-compressible fluid to help prevent unwanted failure or rupture of the cylinder. NFPA 17A also requires the replacement of the cartridge used to expel suppression chemical hoses, o-rings, and burst discs. The proposal below is all-inclusive and includes all parts and labor. You can accept this proposal electronically or contact me directly. Fire Suppression and Kitchen Suppression Repair System is
Kitchen Suppression Inspection FP Semi-Annual
Kitchen Suppression Inspection FP Semi-Annual Deficiency for Ansul R102 4.5 gal: Ansul 4.5 gal system due for 12 yr maintenance Needs: AS79372 3 gal Ansulex AS79694 1.5 gal Ansulex 2 cylinder hydro test 1 AS73022 Double tank cartridge 2 AS79007 Hoses 1 Regulator test 1 G45 gasket 2 AS417911 burst disc
Kitchen Suppression Inspection FP Semi-Annual Deficiency for Ansul R102 6 gal: 2 3 gal tanks are due for 12 year maintenance Needs in-line burst disc Hoses 2019 Regulator test 2021 Cartridge 2020 Need: 2 AS79372 3 gal Ansulex 2 tank hydro 1 AS416970 inline burst disc