Couple learning curve items. Hood baffles got blasted so hard they are no longer usable (we have a back-up set which we will put in, but would prefer they don't get damaged next time, don't have another back-up set. Floor drain was not clogged, the screen just needed cleaned out - it is there to prevent debris from going down the drain and clogging it. Otherwise everything was great, thanks.
Kitchen Exhaust Cleaning Cleaning KEC Semi-Annual - System 3 - Pizza KEC Quarterly - System 1 - Flat Top;Fryer KEC Quarterly - System 2 - Flat Top;Fryer;Oven;Stove Suggested: System 2 needs a 12x8 access panel and a drain plug it’s holding grease at the 90
Kitchen Suppression Repair The Ansul 3gal system has an incorrect and obsolete Ansul cartridge that needs to be replaced. The existing Ansul cartridge has a gold seal which means it was not properly certified by the manufacturer which is a requirement of Ansul. The compliant cartridges will have blue seals. Will need: (1) Ansul LT-30 R Ansul Cartridge Labor - repair Kitchen Fire Suppression System Deficiency: (1) New Ansul Approved Cartridge Needed During the most recent inspection of the Ansul kitchen fire suppression system at Galena Diner, the technician noted that (1) of the Ansul system cartridges was not properly certified by Ansul and must be replaced with Ansul-approved cartridges. The existing cartridge has a gold seal which is a telltale sign that it was not properly certified by Ansul and does not meet the requirements set forth by the manufacturer. The correct Ansul-certified cartridge will have a blue seal which means it has been properly certified by Ansul, the manuf
Kitchen Exhaust Cleaning Cleaning KEC Quarterly - System 1 - Flat Top;Fryer KEC Quarterly - System 2 - Flat Top;Fryer;Oven;Stove