Wet: Install the missing handle on the main drain for system #2. Wet: Install the missing handle on the inspector test valve for system #2. Wet: Install the missing handles on the (2) PIVs located on the south side of the building. Wet: Remove and replace the painted sprinkler head in the maintenance room on the 1st floor. NFPA 25 (5.2.1.1.1) Any sprinkler that shows signs of any of the following shall be replaced; (6.) Paint other than that applied by the sprinkler manufacturer. Wet: Peform the 5-year flow test on the standpipe. NFPA 25 (6.3.1.1) A flow test shall be conducted every 5 years on all automatic standpipe systems to verify that the required flow and pressure are available at the hydraulically most remote hose valve outlet(s) while flowing the standpipe system demand. Perform a 5-year Hydrostatic test on the Fire Department Connection (FDC). NFPA 25 (13.8.5) The piping from the fire department connection to the fire department connection check valve shall be hydros