Wet Pump rm se corner: Perform a 5-year internal assessment of system piping that is due. If an obstruction is present, this can render the sprinkler system not properly operate in the case of a fire (20' lift needed). NFPA 25 (14.2.1.1) An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years or in accordance with 14.2.1.2 to inspect for the presence of foreign organic and inorganic material. Wet Pump rm se corner: Perform a 5-year internal inspection of the Fire Department Connection (FDC) check valve. NFPA 25 (13.4.2.1) Check valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition. Wet Pump rm se corner: INFORMATIONAL PURPOSE ONLY: The hydraulic Placard on both of the systems describes the system design and capacity. These are currently missing. We suggest that the customer reaches out to the installing company to request this information. This would be