Wet Basement: Install the missing caps on the FDC. Prior to installing these, the tech will need to verify that there is no debris in the piping. If debris is present in the connection, a flush will be performed. NFPA 25 (13.8.1) Fire department connections shall be inspected to verify the following: (3.) Plugs or caps are in place and undamaged; (9.) The interior of the connection is inspected for obstructions Wet Basement: Replenish the missing spare sprinkler heads in the spare headbox. NFPA 25 (5.4.1.5.4) The stock of spare sprinklers shall include all types and ratings installed and shall be as follows; Facilities having under 300 sprinklers – minimum of 6 spare sprinklers Wet Basement: Remove and replace the dry pendents in the basement cooler that are dated 2005 & 2009. These have been in service for more than 10 years and are due for testing. Being that there are only (2) pendents, it is cost-effective to replace these. NFPA 25 (5.3.1.1.6) Dry sprinklers that have b