Wet: Remove and replace (3) outdated gauges on the fire pump and controller, (1) on the jockey pump, (1) main feed, (4) on the four floor controls, (2) on the standpipe, and (1) on the suction side of the fire pump. NFPA 25 (13.2.7.2) Gauges shall be replaced every 5 years Wet: Perform a 5-year internal inspection of system check valve, bypass check, and 1st-floor check valve. NFPA 25 (13.4.1.2) Alarm valves and their associated strainers, filters, and restrictions orifices shall be inspected internally every 5 years unless tests indicate a greater frequency is necessary. Wet: Perform a 5-year internal inspection of the Fire Department Connection (FDC) check valve. NFPA 25 (13.4.2.1) Check valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition. Wet: Perform a 5-year Hydro-Static test on the Fire Department Connection (FDC). NFPA 25 (13.8.5) The piping from the fire department connection to th