Job Checkin

11/1/22 Confirmed with Jim Pickell for 11/3/22 at 8:00am DH Sprinkler and Obstruction Investigation Repair 2ND-YEAR DEFICIENCY REPORTED: Remove and replace the outdated water gauges for both systems. NFPA 25 (13.2.7.2) Gauges shall be replaced every 5 years 2ND-YEAR DEFICIENCY REPORTED: The tech will install the missing main drain sign to properly identify system components. 2ND-YEAR DEFICIENCY REPORTED: The tech will install a spare headbox, sprinkler heads, and head wrench for system #1. 2ND-YEAR DEFICIENCY REPORTED: Perform a 5-year internal assessment of system piping that is due for both systems. If an obstruction is present, this can render the sprinkler system not properly operate in the case of a fire. 2ND-YEAR DEFICIENCY REPORTED: The tech will install the missing control valve sign for both systems. Deficiency for Dry Next to O.H. door 12: 5yr internal assessment of system piping is due. Deficiency: 5yr internal valve inspection is due on the FDC check valve, in pit