Jim S.

Jim S.


Job Checkin

10/18 Confirmed with GM Courtney, she said they slow down around 2:00...KM Portable Extinguishers and Kitchen Suppression Inspection Annual Extinguisher Inspection Semiannual Kitchen Inspection Ansul R102-S3 (Chase) (4)280 links (6)Nozzles Ansul R102-S3 (Chase) (2)280 links (4)Nozzles Ansul R102-S3 (Chase) (3)360 links (4)Nozzles Deficiency: Number of Systems failed : 3 Deficiency: Number of Extinguishers Left at Job: 1 Deficiency for Ansul (French Fry Hood) R-102 3 Gallon Chase: All three systems need to have horn/strobe added. No discharge warning device present. Deficiency for Ansul (French Fry Hood) R-102 3 Gallon Chase: Both fryer hood system have improper surface protection. Nozzles need to be changed. Deficiency for Ansul (Grill Hood) R-102 3 Gallon Chase: Clamshells are blocking grill protection . Deficiency: 10# abc fire extinguisher in store room needs a 6yr maintenance. Deficiency: No fire extinguisher by rear Kitchen Exit. Recommend 10# abc.