10/6/22 Confirmed with Jim Y. for 10/10/22 at 11:00amish / Sent email regarding inspection DH Sprinkler Inspection Annual Sprinkler Inspection (1 Wet Sprinkler in Basement) Deficiency: There is no evidence of five-year internal pipe obstruction investigation. Deficiency: There is no evidence of five-year FDC check valve investigation. Deficiency: There is no evidence of five-year FDC hydrostatic test. Deficiency: Spare head box is missing head wrench. Deficiency: Pressure gauges are outdated.