2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for northville, mi


Map of Northville MI
Jim S.

Jim S.


Job Checkin

9/10 Confirmed with Kaitlyn.  Start in the 2nd floor concession and someone will direct you to Kaitlyn.  Understands no cooking and alarms need to be in test. km 9/1 LM for Lew and emailed. km Portable Extinguishers and Kitchen Suppression Inspection Annual Extinguisher Inspection Semiannual Kitchen System Inspection Ansul R102-S3 (2)500 links (2)360 links (7)Nozzles Ansul R102-T9 (3)500 links (3)360 links (16)Nozzles Deficiency: Number of Systems failed : 2 Deficiency for Ansul R-102 9 Gallon Right Side of Hood: The three plenum nozzles on 9 gallon system are improper. Deficiency for Ansul R-102 S - 3G Wall Behind Hood: Electric non fuel source on deep fryer on 2nd floor grill hood does not de energize upon fire system actuation.