Deficiency: Manual pull by front door and heat detector in salon next to front door are disabled at this time after tracking out several issues with zone one. Resistor was moved to room one smoke detector. Upon getting voltage to heat detector in Solon then to the front door pull station the resistor should be moved back to manual pull at the front door as this is the end of the line. Customer is on firewatch but, customer is also a fully staffed assisted living home. Kevin was on site throughout the day and witnessed the change on the FACP from Trouble to Alarm and back to Trouble again after the alarm was cleared. I kept him informed all day of what was going on in the tracking. I moved the resistor from the front pull station to room one. This allowed the entire panel to work properly except for the front pull station and the salon heat detector (salon is in use once a month). Kevin is aware the front two devices are not working and he be repaired. After wire between salon heat dete