2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for saranac, mi


Map of Saranac MI
William S.

William S.


Job Checkin

Maint Room / ITV: Air Handler Room - 2nd Floor: Perform a 5-year internal assessment of system piping that is due. If an obstruction is present, this can render the sprinkler system not properly operate in the case of a fire. NFPA 25 (14.2.1.1) An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years or in accordance with 14.2.1.2 to inspect for the presence of foreign organic and inorganic material. Maint Room / ITV: Air Handler Room - 2nd Floor: Perform a 5-year internal inspection of the Fire Department Connection (FDC) check valve. NFPA 25 (13.4.2.1) Check valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition. Maint Room / ITV: Air Handler Room - 2nd Floor: Replenish the spare sprinkler heads in the spare headbox. NFPA 25 (5.4.1.5.4) The stock of spare sprinklers shall include all types and ratings installed and shall be as follows; Facilities havin