2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for southgate, mi


Map of Southgate MI
Terrence  J.

Terrence J.


Job Checkin

Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) Deficiency: Missing ball drip on FDC pipe 1x1/2” bush 1/2 street 90 1/2” ball drip Suggested: Suggest removing sprinkler heads due to garage door has been removed 1” plugs x2 20’ extension ladder Suggested for Wet Sprinkler: Recalled heads in front seating area. (10) 1/2” 155 SE chrome pendants with escutcheons Deficiency: There is no evidence of 5 year FDC check valve inspection. Deficiency: There is evidence of 5 year FDC hydrostatic test. Deficiency: There is no evidence of 5 year internal pipe obstruction investigation. Deficiency: Missing control valve sign. Deficiency: Missing main drain sign. Deficiency: Mezzanine needs two additional heads added to cover area under it. Deficiency: Inspectors test needs sign. Deficiency: Missing escutcheons in seating area in gym by office area. Will have to lower heads to add escutcheons. (2) 1 x 1/2 RCs (2) 1/2” 155 SR chrome pendants with escutcheons 6’ 1” pipe Defici