2/4/2022 - Jesus approved the appointment for 2/9/2022, 8am. He will be there. Portable Extinguishers and Kitchen Suppression Inspection Annual Extinguisher Inspection Semi-Annual Kitchen Hood Fire Suppression System Inspection (RG-4gl) Deficiency: Prep Hood: Remote pull station is end of line. Deficiency: Prep Hood: 10B- Range is to big for existing hood. Two burners are outside of hood. Deficiency: Prep Hood: System tank 4-gallon Range Gaurd short is out of hydro date. The tank also has old style head on top. Deficiency: Prep Hood: 5 nozzle foil seals are missing. Deficiency: Prep Hood: System does not have a discharge warning device. Deficiency: Main Hood: Shelf over range blocking protection. Deficiency: Main Hood: Improper nozzle over range. Has fryer nozzle needs R nozzle. Deficiency: Main Hood: System has end of line pull station. Deficiency: Main Hood: 10 foil seals are missing.