Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) Deficiency for Riser Counts: Dry pendants are outdated and shall be replaced with new. 2x 12” dry 155 SR dry pendants Deficiency: Sprinkler system will need breakaway lot and chain for control valve along with sign Deficiency: Sprinkler system do for gauge change. Deficiency: Sprinkler system do for internal check of check valve fire department connection as well as system. Deficiency: Fire alarm system has been gutted and does not work at all Deficiency: Fire sprinkler system do for five-year internal obstruction investigation. Deficiency: Sprinkler heads are painted and will need to be replaced. Deficiency: Improper style/amount of spare sprinkler heads.