Terrence J.


Job Checkin

9/28/22 Confirmed with Lindsey via cell for 10/4/22 at 8:00am DH Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) Suggested for Riser Counts: Sprinkler located above tread mills is obstructed recommend installing protection for proper coverage. Lift required 1- 2x1 jack t 1- 1” 90 1- 1” Criticom 1- 1/2” 155 SR brass upright 21-0” 1” 3- 1” loop rings for trap hanger 4- 3/8” tbc 3/8 atr Deficiency: No evidence of five-year internal pipe obstruction investigation. Deficiency: No evidence of 5 year FDC check valve inspection. Deficiency: No evidence of 5 year FDC hydrostatic test. Deficiency: FDC stortz connection missing cap. Deficiency: Gauge is outdated. Deficiency: Missing inspectors tests sign. Deficiency: Painted sprinkler heads need to be removed and replaced with new heads. Deficiency: Improper amount/style of spare sprinkler heads. Deficiency: Missing outer esc found in pool store sales floor Heads may need to be cut longer / head ext. Deficiency: Recommend