Deficiency: Div 3: (12) Duct detector Remote Test Stations (RTS) located in IT Room are not functioning. They are wired, but have no voltage and do not respond when tripped. May need authorized Honeywell dealer to service, EPS performed install. Deficiency: Div 3: (2) 12v12a batteries due for replacement Suggested: Div 4: Wet sprinkler and Preaction systems due for annual inspections. Last inspected (1/2020). EMCOR account. NOTE: Wet system shared and property manager will need notification, as it is dual monitored.