1-5lb 6 yr Kitchen Suppression and Portable Extinguishers Inspection Ansul R-102 6-gallon Prep area: Semi-Annual Kitchen Inspection Equip Desc: (1) Ansul 6 Gallon System Annual Inspection Extinguisher Equip Desc: Inspect (2) Exts Inoperable Deficiency for Ansul R-102 6-gallon Prep area: Detection line failed due to excessive grease buildup under hood Parts needed to complete repair: **7 Ansul detectors **20ft conduit **15ft cables **2.5 labor hours Inoperable Deficiency for Ansul R-102 6-gallon Prep area: Scissor clips in duct area has excessive grease buildup and needs replacement Both 2w duct nozzles area clogged and needs replacement Inoperable Deficiency for 6L K Class Kitchen: K-guard extinguisher located in the kitchen is past due for hydro testing MFD 2014 Deficiency: Number of Extinguishers Left at Job: 1