mike 130p Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 6 GAL Alarm Int: Yes Inoperable Deficiency for Ansul R-102 6 Gallon Kitchen: Ansul 6 gallon: Exhaust fan not functioning. I spoke to Micheal Tate about the Issue which he was already aware of. “The motor seized up” Note: Micheal Tate has a fan motor already, it just needs to be installed. Deficiency for Ansul R-102 6 Gallon Kitchen: An6 Cartridge 101-30 is due for 12 year replacement MFD 2009 Regulator test is due “Last test was performed in 2010