7668 Standish Place
Rockville, MD 20855
(301) 861-0972

Our Top Cities


Job Locations
for district heights, md


Map of District Heights MD
Dwayne  B.

Dwayne B.


Job Checkin

jay 830am Kitchen Suppression Inspection Semi-Annual Kitchen Inspection Equip Desc: (1) PCL 350+350 System ***DURING KITCHEN INSPECTION, CALL BRAD AUPKE OR DAVE CHRISTIE IN THE OFFICE WHILE YOU ARE ON SITE TO GET INFO ABOUT THE HOOD*** Suggested: Hood Inoperable Deficiency: Pcl 350 350 Detection line failed to activate due to excessive grease buildup under hood **Grill lack detection** Parts needed to complete repair: *7 kk2 detectors *3-4 sticks of conduit *30ft steel cable *1 pcl corner pulley and quick seal Inoperable Deficiency: Pcl 350 350 S Clogged duct, plenum & appliance nozzles. Some nozzles have the wrong caps which overtime seized up and damaged nozzles. They need to be replaced ASAP 2 (pyro-NLS-RH2) above 4 burner range 4 (D1 nozzles) Inoperable Deficiency: Chemical found in suppression lines, advise system to be flushed and purged with nitrogen to ensure no clogs in system. Inoperable Deficiency: Pcl 350 350 Electrical shock hazard on fryers Deficiency: Pcl 3