7668 Standish Place
Rockville, MD 20855
(301) 861-0972

Our Top Cities


Job Locations
for edgewater, md


Map of Edgewater MD
Dwayne  B.

Dwayne B.


Job Checkin

Amy 930-11a MUST CALL WHEN ON YOUR WAY 410 913 1942 Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 6 GAL & (1) ANSUL 4.5 GAL Alarm Int: Yes Inoperable Deficiency for Ansul R-102 6 Gallon Main hood: ANSUEL 6 GALLON RESET RELAY INTERLOCKED BUT GAS DOESN'T SHUT OFF Inoperable Deficiency for Ansul R-102 6 Gallon Main hood: ANSUEL 6 GALLON RESET RELAY INTERLOCKED BUT GAS DOESN'T SHUT OFF Inoperable Deficiency for Ansul R-102 6 Gallon Main hood: Ansul 6 gallon Detection line failed to activate due to excessive grease buildup under hood Parts needed to complete repair: 7 Ansul detectors 20ft of conduit 20ft cable 2 corner pulleys 2.5-3 hours labor