Sch. & meet w/ Carlos 530-600 am Kitchen Suppression Inspection ***NEW CONTRACT BEGAN 01/2019*** Semi-Annual Kitchen Inspection Equip Desc: (1) ANSUL PIRANHA 13+13 Inoperable Deficiency for Ansul Piranha 13+13 Kitchen next to mgr office: Detection line failed to activate due to excessive grease buildup under hood 7 corner pulleys 12 Ansul detectors 5 sticks of conduit 50ft steel cable 5-6 hour labor