Debbie 10a Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 3 GAL Alarm Int: Yes Deficiency for Ansul R-102 3 Gallon Left of hood: Ansul 3 gallon: 3 gallon cylinder is due for hydro testing MFD 2009 also regulator test is due. Cartridge: 101-30 MFD 2013 Inoperable Deficiency for Ansul R-102 3 Gallon Left of hood: Ansul 3 gallon: corrosion found in suppression lines. Note: system needs to be flushed with “Ansul flush” and purged with nitrogen to clear all blockages.