Sch. w/ Nkenge / 7 am - 1:30 pm See staff Kitchen not in use Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 6 GAL (Arena) & (1) ANSUL 3 GALLON (Pavilion) Alarm Int: No Inoperable Deficiency for Ansul R-102 6 Gallon Showplace Arena: Ansul 6 gallon: no alarm or bell interlocked to fire suppression system NOTE: exhaust fan doesn’t activate when system was tested Suggested for Ansul R-102 6 Gallon Showplace Arena: Ansul 6 gallon: Fryer removed from under hood (Nkenge Temoney) approved to remove unused drops NOTE: steamer will be put in place of the fryer (Not yet installed)