steve8-12/see steve Kitchen Suppression Inspection Ansul R-102 1.5 Gallon: Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 1.5 GAL Alarm Int: Yes Inoperable Deficiency for Ansul R-102 1.5 Gallon: Customer added new equipment under hood, appliances lack protection. System is currently Ansul 1.5 gallon and may need to be upgraded to a 3 gallon system. Quarter inch pipe needs to be replaced when system is upgraded.