7668 Standish Place
Rockville, MD 20855
(301) 861-0972

Our Top Cities


Job Locations
for fairfax, va


Map of Fairfax VA
Dwayne  B.

Dwayne B.


Job Checkin

jenifer space 2-3am Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (2) ANSUL 3 GAL/(1) ANSUL 6 GAL/(2) ANSUL 9 GAL Alarm Int: Yes Deficiency for Ansul R102 9 GAL H-12: Electrical shock hazard on French fryer station (Hood H-12) Ansul 9 gallon Inoperable Deficiency for Ansul R102 9 GAL H-12: Kitchen Hood:H-7/H-10/H-11 Same deficiency from previous inspection. Shock hazard to electric fryer, no electric shut-off. Charbroiler has been from nozzle protection, it’s been moved to other side of hood. Need to repipe or put back to its corespondent hood and nozzle. Need to remove and plug nozzle drop not protecting anything Electrical shock hazard on French fryer station (Hood H-12) Ansul 9 gallon