lynn / 930-1230 Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 1.5 GAL Alarm Int: Yes Inoperable Deficiency for Ansul R-102 1.5 Gallon: Same deficiency’s remain from last inspections: **System lacks protection and detection Parts needed: add 1 detector above 6 burner range replace 2 pre-ul 300 nozzles over range with (1) 245 & (1) 1F add 1N nozzle over griddle