22645 83rd Ave, S Building D
Kent , WA 98032
206-772-7502

Job Locations
for dupont, wa


Map of DuPont WA
Marc P.

Marc P.


Job Checkin

Annual Fire Alarm, Sprinkler, Fire Pump - no test loop and Standpipe Inspections Deficiency for Silent Knight 5820XL FA-1 / New Customer: Bldg D Elevator 1 floor 2 (across from unit 207) Fire door catches on carpet and doesn’t close Deficiency for Silent Knight 5820XL FA-1 / New Customer: There are 4 different FACP and account #’s. Need to adjust in service trade assets/services Bldg A batteries due for replacement (5) 12v7ah FACP, AES radio, NAC Bldg B batteries due for replacement (3) 12v7ah FACP, AES radio Bldg C batterie due for replacement (3) 12v7ah FACP, AES radio Bldg D batteries due for replacement (3) 12v7ah FACP, AES radio Deficiency for Dry SPK-1 / Pump Room Parking Garage: (2) dry systems in parking garage due for 3 year full trip, will need 8’ - 10’ ladder for low points Deficiency for Patterson Centrifugal FP-C0110577 FPUMP-1 / New Customer: Fire pump gauges are broken and reading incorrectly, need to be replaced (1) 0-300 (1) -30 - 300