Job Checkin

Deficiency Repairs Fire Protection and Backflow Repair Dry SPK-2 North end of basement/Attic: FDC caps are missing. Need FDC flush. Check is at the riser. FEBCO 805YB 019562 BFP-1 1st Floor Fire Sprinkler Room: Backflow failed testing. #2 check valve assembly leaked - Recommend replacement of #2 check valve assembly. 3/4" Febco 805YB Serial #019562 Located in 1st Floor fire sprinkler riser room.