Annual Fire Alarm, Backflow, Sprinkler, Pre-Action, Fire Pump, Fire Extinguisher, Semi-Annual Kitchen Hood & FM-200 Inspections Deficiency for Silent Knight IFP 1000 FA-1 / 1st Floor Behind Hotel Reception Inside Front Office Door: 4th ,3rd, and 2nd floor north tower elevator lobby fire doors did not close. Hands up on the carpet Deficiency for Ansul R102 KISUP-5 / Panasia (Kitchen): Disregard Deficiency for Silent Knight IFP 1000 FA-1 / 1st Floor Behind Hotel Reception Inside Front Office Door: Batteries are due: Silent Knight VIP Main FACP: Qty 2 12V 18AH Bolt Type Silent Knight VIP Booster Panel under FACP: Qty 2 12V 8AH Silent Knight SK-4 Shed Panel FACP Qty 2 12V 8AH By Room IT5 Qty 4 Silent Knight 5895XL Qty 8 12V 8AH Deficiency for Ansul R102 KISUP-5 / Panasia (Kitchen): PANASIA HOOD- 1) wires in control head need to be installed in a junction box outside of the unit. 2) system failed to trip via fusible link line. 3) salamander oven does not have any nozzle covera