22645 83rd Ave, S Building D
Kent , WA 98032
206-772-7502

Job Locations
for kent, wa


Map of Kent WA
Marc P.

Marc P.


Job Checkin

Deficiency for Wet SPK-1 / New Customer: Need to install Knox locking FDC caps (2) Northwest of building (4) Southwest of building For(6) total Deficiency for Dry SPK-9 / New Customer: Dry sprinkler system # 3 has a Reliable B-1 that did not operate and needs replaced. Deficiency for Dry SPK-11 / New Customer: Dry valve will not reset per customer. Did alarm test only. Need to replace dry valve #5 Reliable model C2 6” Take out is 19” Quick opening device was shut down upon arrival Reliable B-1 needs replaced Deficiency for Dry SPK-13 / New Customer: Dry sprinkler system # 6 has a Reliable B-1 that did not operate and needs replaced. Annual Sprinkler and Private Fire Hydrant Inspection