Deficiency Repairs Dry SPK-1 / West Side of Bldg by Elevator 4” CSC AG: Missing (1) spare sprinkler head inside spare head box. Ames 2000B 0003842 BFP-2 / W Side of Bldg Inside in Sprinkler Room: Backflow failed testing. #1 & #2 check valve assemblies leaked - Recommend rebuild of #1 & #2 check valve assemblies. 3/4" Ames 2000B Serial #0003842 Located in fire sprinkler riser room on West side of building. Ames 3000SS 3LM0782 BFP-1 / W Side of Bldg Inside in Sprinkler Room: Backflow failed testing #1 & #2 check valve assemblies leaked - Recommend rebuild of #1 & #2 check valve assemblies. 4" Ames 3000SS Serial #3LM0782 Located in fire sprinkler riser room on West side of building. Febco 850 A00677 BFP-3 / in-front BLDG 811. Near sidewalk, L side drvwy if looking at the road.: Backflow preventer assembly does not have 6 inches clearance under assembly. Assembly passed, but was dug up to test - It is covered in tree roots and buried in dirt. Customer will need to make sure there is 6" of