Deficiency: East bldg sprk Five year ipe Fdc inspections due 1 wet 1 dry 8 water gauges due 1 air gauge due Dry sprinkler wf reports to facp as main wet wf wet reports as dry system flow Deficiency for Dry SPK-3 / Riser Room East Bldg: East bldg dry system due for full wet trip Deficiency for Wet SPK-2 / East Building: East bldg sprk Five year ipe Fdc inspections due 1 wet 1 dry 8 water gauges due 1 air gauge due (North stair standpipe 1 gauge also) Deficiency for Wet SPK-1 / West Building: West bldg Spk 5 year due FDC, IPE, 8 water gauges (Plus 1 water gauge for standpipe) Deficiency for Wet SPK-2 / East Building: East side building in room 302 has a taped concealer Annual Backflow, Sprinkler, Fire Extinguisher, and Stand Pipe Inspection