221 Technology Park Ln
Fuquay Varina, NC 27526
888-998-7772

Local Reviews
for winnsboro, sc


Job Locations
for winnsboro, sc

Matthew M.

Matthew M. Job Checkin

Emergency / Exit Lights and Fire Suppression Inspection


Matthew M.

Matthew M. Job Checkin

Portable Fire Extinguisher Inspection


Matthew M.

Matthew M. Job Checkin

IVR Phone: 844-325-8006 Tracking No: 187231327 Quote derived from inspection work order# 4551489 Initial Services Performed: Semi-Annual Kitchen System Inspection Deficiencies Discovered: (2) Fryers do not have adequate coverage. Scope of Work Proposed: Install (2) swivel adapters on appliance drops covering fryers. Exclusions: Electrical and /or Plumbing work (if required). Permits (if required). Any changes mandated as a result of an Authority Having Jurisdiction (AHJ) review of the proposed scope of work. Fire Suppression Repair


Matthew M.

Matthew M. Job Checkin

Fire Suppression and Emergency / Exit Lights Inspection


Matthew M.

Matthew M. Job Checkin

Special Instructions: If tech is turned away for any reason, please call CF before leaving property. We can rectify the situation with corporate to avoid any return trips. IVR Phone: 844-325-8006 Tracking No: 145116226 Initial Services Performed: Semi-Annual Kitchen System Inspection Deficiencies Discovered: Wendy's During the detection line activation test the automatic detection portion of the system failed to operate as designed. The conduit was found to be loaded with grease which is believed to be the cause of this failure. Scope of Work Proposed: Replace (9) detectors, all conduit and all detection line cable from the end of line detector bracket back to the system control. Exclusions: Electrical and /or Plumbing work (if required). Permits (if required). Any changes mandated as a result of an Authority Having Jurisdiction (AHJ) review of the proposed scope of work. Fire Suppression Repair


Matthew M.

Matthew M. Job Checkin

IVR Phone: 844-325-8006 Tracking No: 142300594 Fire Suppression Inspection


Matthew M.

Matthew M. Job Checkin

IVR Phone: 844-325-8006 Tracking No: 143506014 Customer PO: 611719 Filter Cleaning Cleaning


Matthew M.

Matthew M. Job Checkin

IVR Phone: 844-325-8006 Tracking No: 142304877 Fire Suppression Inspection


Matthew M.

Matthew M. Job Checkin

Fire Suppression and Portable Extinguishers Inspection


Matthew M.

Matthew M. Job Checkin

IVR Phone: 844-325-8006 Tracking No: 139123790 Portable Extinguishers Inspection


Matthew M.

Matthew M. Job Checkin

IVR Phone: 844-325-8006 Tracking No: 133298529 Customer PO: 596857 Filter Cleaning Cleaning


Matthew M.

Matthew M. Job Checkin

IVR Phone: 844-325-8006 Tracking No: 134223344 Initial Service Performed: Annual Portable Fire Extinguisher Inspection as per NFPA 10 Deficiencies Identified: During the recent inspection of the portable fire extinguishers various units as listed below were identified and documented as requiring additional maintenance in order to be certified. Below is a line item listing of each unit in need of additional maintenance and the type of maintenance required. Upon completion of this work each unit will be certified and tagged compliant. (1) 10LB ABC extinguisher(s) is due for hydro-static testing. (1) K-Class extinguisher(s) is due for hydro-static testing. Scope of Work: Definitions of what each line item listed service below is as follows: Replace (1) 10LB ABC extinguisher(s) Perform hydro-static test on (1) K-Class extinguisher(s) -Hydro-Static Testing-Every 12 years portable fire extinguishers with dry chemical are required to be discharged, broken down and put through a specialized lo