26 Hampshire Drive
Hudson, NH 03051
(800)244-7531

Local Reviews
for franklin, ma

Rated 4.0 out of 5 stars based on 1 customer reviews

great

Fast work got my guys out working quick. informative and thorough

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for franklin, ma

Nicholas L.

Nicholas L. Job Checkin

Gas Station Suppression Inspection GAS STATION Please make sure to email a copy of the GSSUP report to the gas station manager on duty & Ken Silvia whom is the Stop & Shop gas stations supervisor.


mark g.

mark g. Job Checkin


Jim C.

Jim C. Job Checkin


Matt N.

Matt N. Job Checkin

Portable Extinguishers Inspection


Nicholas L.

Nicholas L. Job Checkin

Gas Station Suppression Inspection GAS STATION


Nicholas L.

Nicholas L. Job Checkin

Recently one of our licensed technicians was at your location to perform the service on your fire suppression system. During that inspection the following deficiency was found. Fire suppression system cylinder is due for hydro-test. A pressure test, rebuild and refill is required. DOT and the system manufacturer require that these system cylinders are tested every 12 years. NFPA 17A section 7.5 states; 7.5.1The following parts of wet chemical extinguishing systems shall be subjected to a hydrostatic pressure test at intervals not exceeding 12 years: (1) Wet chemical containers (2) Auxiliary pressure containers (3) Hose assemblies Cartridge is at the 12 year mark and must be replaced. System regulator is reqy=uired to be tested at the same time Repair of these deficiencies is essential to overall life safety. Please see attached quote. If you have any questions, feel free to call me. Thank you Brian 603-305-3137 Fire Suppression Repair Ansul R102 3g Deli Rear: Kitchen System: 3g tank i


Nicholas L.

Nicholas L. Job Checkin

Recently one of our licensed technicians was at your location to perform the service on your fire suppression system. During that inspection the following deficiency was found. Fire suppression system cylinder is due for hydro-test. A pressure test, rebuild and refill is required. DOT and the system manufacturer require that these system cylinders are tested every 12 years. NFPA 17A section 7.5 states; 7.5.1The following parts of wet chemical extinguishing systems shall be subjected to a hydrostatic pressure test at intervals not exceeding 12 years: (1) Wet chemical containers (2) Auxiliary pressure containers (3) Hose assemblies Cartridge is at the 12 year mark and must be replaced. System regulator is reqy=uired to be tested at the same time Repair of these deficiencies is essential to overall life safety. Please see attached quote. If you have any questions, feel free to call me. Thank you Brian 603-305-3137 Fire Suppression Repair Ansul R102 3g Deli Rear: Kitchen System: 3g tank i


Shem H.

Shem H. Job Checkin


Brenda K.

Brenda K. Job Checkin

Annual inspection and service of Fire Extinguishers and emergency lights.