Gas Station Suppression Inspection GAS STATION - QTY 1 PGS-75 - 6yr 2013 x1 PGS-75 - 6yr 2016 x7 PGS-35 - 6yr 2017 x2 Please make sure to email a copy of the GSSUP report to the gas station manager on duty & Ken Silvia whom is the Stop & Shop gas stations supervisor.
Fire Suppression Inspection kitchen suppression parts
Fire Suppression Inspection KITCHEN SYSTEM - QTY 1 R102 6G - Hydro 2014(2)
Fire Suppression Repair Parts for Kitchen inspection
Fire Suppression Inspection KITCHEN SYSTEM - QTY 1 R102 6G - Hydro 2014(2)
Gas Station Suppression Inspection GAS STATION - QTY UNKNOWN
Fire Suppression Inspection KITCHEN SYSTEM - QTY 1 R102 6G - Ansul Email Watchman 14 gas station fire suppression
Fire Suppression Inspection KITCHEN SYSTEM - QTY KS ALL INCLUSIVE Deficiency for Pyro Chem PCL-460 2 Kitchen: System is non compliant due to improper coverage of the chargrill and salamander broiler. Nozzles need to be repiped so that they are postioned correctly per manufacturer manual. Also there is lots of grease build up on and in the conduit above the Chargrill I recommend getting this section of conduit replaced. Grease build up inside conduit could stop the system from working properly. Clean out the best I could for the mean time. see pictures