Gas Station Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection GAS STATION SYSTEM - QTY 1 ATD35 x 2 & ATD75 x 8 All 2014 GS TO DO FX AT SAME TIME FIRE EXTINGUISHERS - QTY 4 FX TO DO GS AT SAME TIME EMERGENCY LIGHT SPOT CHECK - QTY 12 REPAIR AS NEEDED EL TO BE DONE WITH GS Deficiency for Pyro Chem ATD-75x8 & ATD-35x2 10: Suppression: Ansul Z10 panel is not listed by Pyro Chem to be used with the Attendant system. Also the Z10 panel is not monitored for trouble by the building alarm. Confirmed 10/24/16 ML Confirmed 4/6/17 CJA Confirmed 10/16/17 ML Confirmed 10/24/18 NL Deficiency for Pyro Chem ATD-75x8 & ATD-35x2 10: Suppression: Several of the pipe networks in this system are incorrect. 2 cylinders have 6 changes in direction (4 allowed)(end of island for pumps 5-8). Two cylinders (ATD 35) use all 3/4" pipe (mfg requires 1" to T1). The nozzle clusters for the 2 ATD35 cylinders are aimed incorrectly. The last elbow in the end of island pipe networks (x4)


Nicholas L.

Nicholas L. Job Checkin

Gas Station Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection GAS STATION SYSTEM - QTY 1 ATD35 x 2 & ATD75 x 8 All 2014 GS TO DO FX AT SAME TIME FIRE EXTINGUISHERS - QTY 4 FX TO DO GS AT SAME TIME EMERGENCY LIGHT SPOT CHECK - QTY 12 REPAIR AS NEEDED EL TO BE DONE WITH GS Deficiency for Pyro Chem ATD-75x8 & ATD-35x2 10: Gas Station: Previous deficiencies still exist. See pictures