Mike did a great job installing a Fire Trace system for a small test cabinet in our lab.
FireTrace DLP Novec1230 Clean agent Asset protection Suppression install
Portable Extinguishers and Fire Suppression Inspection FIRE EXTINGUISHERS - QTY UNKNOWN - ALL INCLUSIVE KITCHEN SYSTEM - QTY UNKNOWN - ALL INCLUSIVE Deficiency: Main system is non compliant. No alarm connected to system. No electrical shut down. Range has improper coverage. Nozzles need to be relocated to the front edge of the range aimed to the center of the burners. Nozzles are too low as well. Griddle #1 has improper coverage. Nozzle needs to be relocated within 0-2 inches along the edge of the cooking surface and aimed at the center. Griddle #2 has improper coverage. Nozzles need to be relocated within 0-2 inches along the edge of the cooking surface and lowered. Chargrill has no Nozzle protecting it. Fryers have the wrong nozzles protecting them. They need to be changed to 3N nozzles and lowered to a maximum height of 35 inches. By added a nozzle to the chargrill and changing the nozzles for the fryers the system will need a additional cylinder in order to have enough flows to p
Fire Suppression and Portable Extinguishers Inspection KITCHEN SYSTEM - QTY - ALL INCLUSIVE PCL-300 - 2 CYLINDER FIRE EXTINGUISHERS - QTY 7 ALL INCLUSIVE Suggested: Back shelf exceeds manufacturer specs for over hang. Shelf measures at 12". need to be 11" or shorter. Or removed all together.