see comment below Fire Suppression Inspection KITCHEN SYSTEM - ZONE 1 BUCKEYE, BFR-20 new style cly HYDRO: 2007 KS TO BE DONE WITH FX Adjust appliance coverage to line up with appliances now under the hood. Deficiency: Fryer and griddle protection needs to be repiped so that appliances are properly protected Bfr 20 (2007) will be due for hydro 1/19 8 19.5"x19.5" mesh filters need to be replaced Not connected to building fire alarm