Gas Station Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection GAS STATION - PGS70 x 6 - 2013 GS TO BE DONE WITH FX FIRE EXTINGUISHERS - QTY 4 FX TO DO WITH GS EMERGENCY LIGHT SPOT CHECK - QTY 10 REPAIR AS NEEDED EL TO BE DONE WITH GS


Chuck S.

Chuck S. Job Checkin

Portable Extinguishers Inspection


Nicholas L.

Nicholas L. Job Checkin

Gas Station Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection GAS STATION - QTY 1 GS TO BE DONE WITH KS FIRE EXTINGUISHERS - QTY 7 FX TO DO WITH GS EMERGENCY LIGHT SPOT CHECK - QTY 13 REPAIR AS NEEDED EL TO BE DONE WITH GS Inoperable Deficiency for Pyro Chem ATD80SBC / ECH3 1920#: Gas station system: One cylinder has leaked down outside of the green. Two cylinders do not have minimum pipe diameters between elbow and distribution block. All cylinders require bracing before distribution block. PAC200 is not using a proper bracket for mounting. Noted 3/19/2018: PAC200 under counter in store is due for hydrostatic test. Inoperable Deficiency for Pyro Chem ATD80SBC / ECH3 1920#: System is inoperable due to one of the ATD80 cylinders above pump 11 has lost pressure and will need to be serviced The PAC200 on canopy is not in a bracket and the other PAC200 (under counter) is due for hydro. None of the piping on top of the canopy is braced. 2 cylinders do not hav


Chuck S.

Chuck S. Job Checkin

Portable Extinguishers Inspection