Job Checkin

Upstairs AC Not Keeping Up Units pressures and temperatures are good 19 degree drop out of the vents Only fiberglass batts in the attic Temp came down a degree while I was there Filters are clean Drains very slow Customer wants other unit checked out We will schedule to come back out to check the main unit and also blow that drain with a drain gun 7/16 drain cleared on Goodman unit Trane unit (older) was running with a blown capacitor for the compressor and a weak cap for the fan motor. Replaced with a dual for cost effectiveness On the refrigerant circuit it seems like we’re having some expansion valve issues. Coil runs at 30 degrees with 20 degrees of superheat and subcooling. Major loss in efficiency and possibility of coil freezing into a solid block of ice Will talk to the office and make sure the cooks see this. Being that they no longer make the refrigerant in this unit anymore it may make more sense to them to think about replacement in the future