130 S. DIVISION ST
Carterville, IL 62918
618-985-2502

Job Locations
for marion, il


Map of Marion IL
Steve R.

Steve R.


Job Checkin

Unit 1, conference room. Found coil frozen, added 5lb r410a Unit 2, SW offices. unit out of gas, found txv leaking. Ordered new txv Unit 3, lobby. Out of gas, holds 20 lbs, need to leak search Unit 4, conference room. Added 4 lb r410a Unit 5, 3 lb r410, possible txv issue indoors Unit 2 replaced txv, turned on system, compressor hardly pumps and then overheats, this unit has had a reversing valve and txv go bad in the last year, I suspect those issues have contributed to the compressor going out. Would recommend replacement Unit 3 leak searched unit, pressure tested, found Schroeder’s leaking. Replaced all 3, added 16 lbs 410a and system is cooling