Checked the Under Counter Refrigerator unit and found it on. The thermometer inside the box said 46 degrees Fahrenheit. Checked out the unit. It was cycling off on temperature and it felt cold. Put a thermometer inside the box. It said the unit shut off at 35 degrees Fahrenheit. The unit did not come on at 41.9 degrees Fahrenheit so I turned the control a half turn clockwise until the compressor started. Allowed the unit to drop temperature again. The low pressure control is sticking and should be replaced. Need to get one. The customer would like a quote. Note: quoting additional repairs, closing out this work order