Performed maintenance on split heat pump. Found drain line very clogged up, found secondary panel loaded with water, found weak capacitor in indoor and outdoor coil. Found very dirty coils, found water inside the cabinet of the indoor blower. Washed outdoor coil. Found blower motor over amping, replaced capacitor in indoor motor because it was really low. Rated 15 MFD, testing 7.5 MFD. Customer is getting home warranty in the next couple of days. Customer used $50.00 coupon on service agreement. Customer still has 2 visits left and also a plumbing inspection which is included. Thank you for choosing Cool Touch!