Jesse E.

Jesse E. Job Checkin

Thermostat was wired wrong. Connected R and Blue to common instead of B. System is on and cooling.


Kressy D.

Kressy D. Job Checkin

Bad 35/5 capacitor Replaced capacitor and checked charge Replaced 30x14 Filter


Kressy D.

Kressy D. Job Checkin

Condenser fan motor locked up, installed new fan motor and system still wasn’t cooling System is out of r22 Customer wanted to add r22 and when I started I noticed that we have a leak inside of condenser Took fan motor off and turned breaker off at unit


Kressy D.

Kressy D. Job Checkin

Found no leak in any of the closets.. system is operating as it should Checked closets for water and walls and carpet are dry System was running when I arrived and shut off because it hit temp


Jason B.

Jason B. Job Checkin

Checked AC. Condenser coil had some debris from Cottonwood trees. Sprayed coil and adjusted charge. Unit had 17.3 degree temp split.


Kressy D.

Kressy D. Job Checkin

Changed 45 capacitor Washed condenser Added stop leak Added 1lb r22 System cooling well


Kressy D.

Kressy D. Job Checkin

Bad capacitor Replaced capacitor and system fired right up and is cooling when I left


Kressy D.

Kressy D. Job Checkin

Blower motor burnt wire and not coming on again, coil is frozen over again Filter is new and when i fixed wire last week and got motor running it wasn’t pulling high amps so our problem is that we are low on refrigeration and it runs long enough to for coil to freeze then there is no air going across motor and it’s running hot until the wire melts System needs replaced


Kressy D.

Kressy D. Job Checkin

Condensation pipes for both systems are outside of the drain so they have both been running water into apt 117 I put both pipes back inside of drain


Kressy D.

Kressy D. Job Checkin

Thermostat not sending call to unit Replaced thermostat Ac was really dirty as was the filter so I changed filter and washed condenser System cooling when I left


Kressy D.

Kressy D. Job Checkin

No one home and no one onsite to open apt


Kressy D.

Kressy D. Job Checkin

Apt 201 Found thermostat not activating cool mode so I jumped wires together and ac kicked on I then noticed that system was low on refrigeration I called Madison and explained issues and she said leave for now


Jason B.

Jason B. Job Checkin

Estimate to replace 33 units at apartment complex


Jesse E.

Jesse E. Job Checkin

Resident said unit started working, checked and system is cooling.


Jesse E.

Jesse E. Job Checkin

No contact made, tech on scene from 1:00 to 3:00.