Homeowner stated that the D/S unit is not cooling,,,, Started diagnostic at the condenser unit after setting the thermostat to cool,,, noticed the compressor not running, tested capacitor ( 70 mfd run capacitor),, tested ok,, checked for proper voltage coming in to the unit tested ok ,, noticed the compressor was humming, tried a hard start kit hopping this was going to help it start working, had same results, at this point thermal overload sensor inside the compressor got open because was overheating, cooled down with water, tried again,,, had same issue,,, COMPRESSOR IS LOCKED UP AND NEEDS TO BE REPLACED. Also condenser unit is very dirty,,, needs to be washed a soon as possible because it’s not breathing properly,, this causes severe damages to the unit.,,,,will be washed after repairs.