No cool service call performed today. Checked system operations, 240v at AH, 24v at transformer, system calling for cool with no response from condenser, confirmed 24v at CU - no 240v, confirmed 240 at disconnect, no 240 after breaker, replaced faulty breaker with new, system operations normal.