Found a bad blower motor. Replaced the blower motor and tested the blowers operation.
Completed the maintenance inspection. Replaced the media filter.
Completed the maintenance inspection. Replaced the media filter
Completed the maintenance inspection. Replaced the media filter
Found the system off on code 77 and 95. Checked the grounds and the compressor windings. I've reset the system and everything came back on and js cooling down for now. I would recommend replacing the inverter. Putting in a parts order and reschedule to return with the part. Installed the inverter and got the system up and cooling. Note: code 99 on system number 2. Need to order a part and schedule to return. Returned and replaced the condenser fan motor on system 2 the two ton.
Found the system off on code 77 and 95. Checked the grounds and the compressor windings. I've reset the system and everything came back on and js cooling down for now. I would recommend replacing the inverter. Putting in a parts order and reschedule to return with the part.
1st year warranty System shutting off on float switch safety. Cleaned and flushed drain line. Restarted and tested cooling and drain line.
Replaced shorted dual run capacitor. Restarted cooling 10 parts and labor.
Located and repaired 230 volt connection to contactor. Replaced weak run capacitor Charge to credit card on file
repaired leak on liquid line by filter drier. Leak tested and evacuated system. Rplaced lost 410a. Restarted and tested sub cooling. Warranty
Found no issue with the air conditioning system itself the problem is with the generac system, remove the wiring from the air handler breaker and connected the air handler wiring to the air handler breaker to allow cooling until the customer get generac out to fix the problem
Found error codes 41 and 44. Found a bad blower motor. Also the system is in poor condition and should be replaced.
Found the noise coming from the reversing valve. After working on the unit for about ten minutes the noise went away. Could be an intermittent noise from the reversing valve. I also noticed a refrigerate leak at the condenser coil. The air handler is from 2016 but the condenser's serial number is faded off and appears to by older as all of its screws and bolts.are rusting.