8021 W. Gulf to Lake Hwy
Crystal River , FL 34429
352 795 2665

Local Reviews
for clearwater, fl

Rated 4.9 out of 5 stars based on 13 customer reviews

David is very knowledgeable professional and courteous

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

Bay Area Air conditioning is a top their company and every employee that we have dealt with has provided exceptional service. Mr. Milligan was here on an annual service call, performed the service and left detailed notes on the system and performance. He also fixed a problem with the UV light and the electrostatic filter that I was unaware of. Thanks.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Service

As usual, Bay Area does a great job! Highly recommend them. The service man was courteous and did a wonderful job.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service, pleasant service man.

Got here right at 8 AM, did his work and on his way.

  • Overall Experience
  • Quality
  • Price
  • Convenience

So far we are very happy with your service and pricing. Since 5 stars are perfect we may hold back a star just to keep you improving.

We had Dave check Freon which was up to specs. Dave also leak tested the A- coils and compressor and was not able to find any leaks. When the unit was installed the refrigerant lines were not replace since they run under the concrete floor through a conduit. We assume the lines are original and my be corroded and almost impossible to remove to install new lines but no one has attempted the task. We plan to have your company move the compressor off our patio and new lines installed at that time. However, we must gain approval and permits from On Top of the World Management. If they approve the move and issue a permit, we will contact you to complete the job.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Very professional, knowledgeable and friendly...all important to me!!!

Every step of the way was efficient and professional. Very pleased and would refer to anyone with confidence.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Very efficient from the first phone call....very pleased

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service, Great Employees

Have been a customer since 2012 and heartily recommend Bay Area! Thanks, Glenn!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent response time on Saturday!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service - As always!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for clearwater, fl

Cliff P.

Cliff P. Job Checkin

Found the system off on code 77 and 95. Checked the grounds and the compressor windings. I've reset the system and everything came back on and js cooling down for now. I would recommend replacing the inverter. Putting in a parts order and reschedule to return with the part. Installed the inverter and got the system up and cooling. Note: code 99 on system number 2. Need to order a part and schedule to return. Returned and replaced the condenser fan motor on system 2 the two ton.


Cliff P.

Cliff P. Job Checkin

Found the system off on code 77 and 95. Checked the grounds and the compressor windings. I've reset the system and everything came back on and js cooling down for now. I would recommend replacing the inverter. Putting in a parts order and reschedule to return with the part. Installed the inverter and got the system up and cooling. Note: code 99 on system number 2. Need to order a part and schedule to return. Returned and replaced the condenser fan motor on system 2 the two ton.


Cliff P.

Cliff P. Job Checkin

Needs rescheduled


Cliff P.

Cliff P. Job Checkin

Needs rescheduled


Cliff P.

Cliff P. Job Checkin

Found the system off on code 77 and 95. Checked the grounds and the compressor windings. I've reset the system and everything came back on and js cooling down for now. I would recommend replacing the inverter. Putting in a parts order and reschedule to return with the part.


Cliff P.

Cliff P. Job Checkin

Found the system off on code 77 and 95. Checked the grounds and the compressor windings. I've reset the system and everything came back on and js cooling down for now. I would recommend replacing the inverter. Putting in a parts order and reschedule to return with the part.


Cliff P.

Cliff P. Job Checkin

1st year warranty System shutting off on float switch safety. Cleaned and flushed drain line. Restarted and tested cooling and drain line.


Cliff P.

Cliff P. Job Checkin

1st year warranty System shutting off on float switch safety. Cleaned and flushed drain line. Restarted and tested cooling and drain line.


Marc M.

Marc M. Job Checkin

Customer stated stopped cooling in the middle of the night. Float switch did not trip, unit continued to run. Checked capacitor, refrigerant charge, split temps. Customer said heard sound when occurred and had storm. System straight cool and suspect power drop cause compressor off on ol from run backwards momentarily.


Cliff P.

Cliff P. Job Checkin

Replaced shorted dual run capacitor. Restarted cooling 10 parts and labor.


Cliff P.

Cliff P. Job Checkin

Replaced shorted dual run capacitor. Restarted cooling 10 parts and labor.


Jeff W.

Jeff W. Job Checkin

Compressor wire burnt and disconnected. Repair wire and test. System operating at this time. Recommend replacing system. Recall, customer states CC on file. New equipment quote left at last call.


Cliff P.

Cliff P. Job Checkin

Located and repaired 230 volt connection to contactor. Replaced weak run capacitor Charge to credit card on file


Cliff P.

Cliff P. Job Checkin

Located and repaired 230 volt connection to contactor. Replaced weak run capacitor Charge to credit card on file


Cliff P.

Cliff P. Job Checkin

repaired leak on liquid line by filter drier. Leak tested and evacuated system. Rplaced lost 410a. Restarted and tested sub cooling. Warranty