8021 W. Gulf to Lake Hwy
Crystal River , FL 34429
352 795 2665

Local Reviews
for hudson, fl

Rated 4.9 out of 5 stars based on 81 customer reviews

Very Responsive Company!!

Excellent and Professional service.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great

Matt was the technician that worked on the air and heat and did a very good job. He found the problem and we are good to go. Thankyou. Larry. Dobiak

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

Jeff knew just what the issue was,and fixed it in a fast and friendly way.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

I would recommend this company

  • Overall Experience
  • Quality
  • Price
  • Convenience

AC Ductless

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Tech & Tuneup

I have had a great experience with this company from when I replaced my system 7 years ago and again today when I had the drain line cleaned out and an annual tuneup. The Tech was very professional and informative and the cost of the service was very reasonable.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome experience

Top notch service

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service .the best of the best

my 3rd experience.honestly could not ask for better service.the problem was solved in the first 10 minutes .2x at my place and once at my moms.i already recommended them to 2 of my neighbors.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Both

Great Guy Mark

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for hudson, fl

Pete C.

Pete C. Job Checkin

Tune up complete Replaced infinity air filter


Marc M.

Marc M. Job Checkin

When arrived checked system in heat. Found air handler blower and electric heat running but heat pump not running. Found no call for outdoor unit from thermostat. Verified configuration and found tstsat configured for straight cool operation with electric heat only. Reconfigured thermostat for correct equipment type. All operating properly now.


Cliff P.

Cliff P. Job Checkin

found transformer blown on 24 volt side. Also found coil on contactor shorted to ground. Contactor 24 volt coil short caused transformer to blow ( burn out ). Installed new parts and tested system. Note: weak 24 volt coil on heat strip shorted and caused the issues.


Cliff P.

Cliff P. Job Checkin

found transformer blown on 24 volt side. Also found coil on contactor shorted to ground. Contactor 24 volt coil short caused transformer to blow ( burn out ). Installed new parts and tested system. Note: weak 24 volt coil on heat strip shorted and caused the issues.


Cliff P.

Cliff P. Job Checkin

Found a blown fuse within the air handler. Removed the fuse and searched for a short. I did find a damaged wire within the condenser and loose wiring at the thermostat. Repaired the wire and tightened the connections at the thermostat. 30 day warranty.


Cliff P.

Cliff P. Job Checkin

Found a blown fuse within the air handler. Removed the fuse and searched for a short. I did find a damaged wire within the condenser and loose wiring at the thermostat. Repaired the wire and tightened the connections at the thermostat. 30 day warranty.


Jeff M.

Jeff M. Job Checkin

Annual ac tuneup and cleaning. I checked system operations. I checked amp draws. I checked static pressure and temp split. I waxed outdoor unit. I cleaned evaporator and condenser coil and purifier. I flushed drainline. I changed filter furnished by homeowner. No issues at this time.


Cliff P.

Cliff P. Job Checkin

Confirmed that blower motor has failed . Sent information to parts department. Cost of new motor is pending. Also left quotes for new system per customer request. System is about 10 years old. If customer decides on new system need to make sure existing electrical panel is up to code.


Cliff P.

Cliff P. Job Checkin

Confirmed that blower motor has failed . Sent information to parts department. Cost of new motor is pending. Also left quotes for new system per customer request. System is about 10 years old. If customer decides on new system need to make sure existing electrical panel is up to code.


Cliff P.

Cliff P. Job Checkin

Defrosted system. Tested and found system low oh refrigerant. Leak searched system several times. Found freon steadily leaking at service port on evaporator coil. Tightened Schrader core and replaced plastic cap with brass cap to stop service port from leaking. Found no other leaks. Replaced lost refrigerant. Added three pounds of 410a


Cliff P.

Cliff P. Job Checkin

Defrosted system. Tested and found system low oh refrigerant. Leak searched system several times. Found freon steadily leaking at service port on evaporator coil. Tightened Schrader core and replaced plastic cap with brass cap to stop service port from leaking. Found no other leaks. Replaced lost refrigerant. Added three pounds of 410a


Cliff P.

Cliff P. Job Checkin

service call completed, 3 amp fuse blown upon arrival, check system and trace low voltage, found high pressure switch wire exposed and were making contact with Cooper tube from the compressor, isolated wires and replace fuse ( client provided fuse ) advised client system condition and provide with options for new system replacement send on the email on file , financing options are available call to scheduled


Cliff P.

Cliff P. Job Checkin

service call completed, 3 amp fuse blown upon arrival, check system and trace low voltage, found high pressure switch wire exposed and were making contact with Cooper tube from the compressor, isolated wires and replace fuse ( client provided fuse ) advised client system condition and provide with options for new system replacement send on the email on file , financing options are available call to scheduled


Jeff M.

Jeff M. Job Checkin

upon arrival the float was tripped. I removed panels and vacuumed slime from pan and drainline. Then I flushed drainline multiple times with dawn. The stat came back on and ready when set point is needed.


Cliff P.

Cliff P. Job Checkin

service call, system down upon arrival due client replace contactor, system has a reset push button, that can cause due a short or overload on the system, unit over 15 years old, system heavily impacted with rust, advised clients system condition, at this moment system is operating at this time