06/26/2025- I arrived on site to find the compressor tripping the breaker on startup, however when I checked the compressor it was not shorted to ground or short circuited in general. The windings were also is spec, so I checked the other high voltage components and found the 45/5 capacitor and found it dead on the hermetic side. This caused the compressor to pull too much power from the house on startup, which would trip the 30 amp breaker. After replacing the dead capacitor I tested the unit and it came on without issue. I tested the unit several times on startup and the unit functioned properly each time. I have verified that the unit is working and cooling properly at the time of service.